Erlend site power flows

Move the sliders or pick a scenario to see where power goes between the grid, the wind turbine, the solar and the battery. The hybrid inverter runs in self-use mode. Run the clock to watch the battery fill and empty.

Power flow diagram CT1 CT2 CT3 Inv CT DCDC
Grid–
Battery–
Generation used on site–
Battery time–
House load supplied by

What the Shelly Pro 3EM reads

ChannelCircuitReading

Positive means flowing into the house. House load = CT1 + CT2 + CT3.

How the inverter decides

  • Its CT sees export: it charges the battery with the surplus, from solar or turbine, up to its max rate.
  • Its CT sees import: it discharges just enough to bring the grid back to zero.
  • Battery full: surplus exports. Battery at its 10% reserve: the house imports.
  • If its CT can't see the turbine, it thinks the house is importing while the turbine is exporting, and drains the battery to the grid. Fix: CT on the grid tails, upstream of where the turbine joins.

Figures are illustrative. Pylontech US2000 is taken as 2.4 kWh per module. Whether the inverter charges from turbine surplus on the AC side depends on its make and settings. Inverter conversion losses are ignored. Site plan: whiteboard.